hidden

Transformer Oil Filtration Machine Manufacturers in Delhi Ncr

Transformer Oil Filtration Machine Manufacturers in Delhi Ncr

Detailed Specification



S. No.
PARAMETERS
UNITS
BEFORE FILTRATION
AFTER FILTRATION
1
Break Down Voltage with 2.5mm Electrode Gap. kV 25 >50- 70
2
Moisture Removal ppm 50-100 Up to < 5 - 10
3
Neutralization Value (With IRC Option Only) mg of KOH/g 0.5 < 0.1
4
Particle size (Filter Fineness) Micron Visible < 1
5
Gas Content % Vol./Vol. <10% < 0.1%

Contact Us

Let's Get In Touch

Rayon Energy Pvt Ltd


L3, First Floor, Nyay Khand -1, Indirapuram, Ghaziabad- 201014

Office Telephone :0120 4139773
Mobile : +91 9013241436, +91 7669021285

mail : sales@rayonindia.com
Inquiries : rayonfiltration110@gmail.com

Business Hours Monday - Saturday: 10am to 6pm Sunday: Closed

hidden

Our Services  |    Ultra High Vacuum Transformer  |    Transformer Oil Filtration Plant

  |    Delhi

© 2019 Rayon Energy. Made With Love By webtechgraphics.com